Viessmann Boiler: Set an individual DHW time program
Set an individual DHW time program on a Viessmann boiler: Use this instead of automatic mode when DHW timing must be set separately. The same steps apply to the DHW re-circulation pump.
Applies to: Domestic hot water time program and DHW re-circulation pump
How to fix set an individual dhw time program: step by step
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button until it lights up.
- Press the time program button until 'DHW time program' shows.
- Select 'Individual?' if it is not already shown.
- Confirm.
- Choose '1-7' for identical days, or a weekday for individual days, then confirm.
- Set DHW phase 1 ON time, confirm, set phase 1 OFF time, confirm.
- Repeat for DHW phases 2 to 4.
- Close the hinged cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitocontrol-S, VD2/CT3/CM2 operating instructions, pp. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.