Viessmann Boiler: Sensor capillaries and cable routing
Sensor capillaries and cable routing on a Viessmann boiler: Sensor capillaries must not be kinked, or the sensors will not work properly. Cables and capillaries must not sit directly on the cast iron heat exchanger.
Applies to: Vitotronic control installation
How to fix sensor capillaries and cable routing: step by step
- Keep sensor capillaries straight and unkinked.
- Route all cables and capillaries between the nylon-backed insulation and the metal enclosure panels.
- Coil any excess cabling and tuck it between the side panel and the insulation.
- Tighten the strain reliefs.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitorond 100 installation and service instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.