Viessmann Boiler: Select the boiler sequence

Updated · by Aurora Star Tech Inc.

Select the boiler sequence on a Viessmann boiler: Set the lead boiler and the boiler sequence in a cascade system.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300-K MW1S cascade

How to fix select the boiler sequence: step by step

  1. In coding 2, if required, set coding addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
  2. Press the two buttons shown together for about two seconds.
  3. Select the boiler sequence with the arrow buttons. Pressing both buttons together exits without saving.
  4. Press OK to save the sequence.
  5. In coding 2, set coding addresses 38, 41, 42, 43 and 44 as described in the function description.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 81. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.