Updated · by Aurora Star Tech Inc.

Select heating circuit pump and primary piping on a Viessmann boiler: Boiler is for closed loop, forced circulation hot water systems only. Pump sizing must be based on accurate flow and pressure drop calculations, including DHW sizing.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W WB1B 26 and 35

How to fix select heating circuit pump and primary piping: step by step

  1. Use standard friction loss method for pipe sizing and keep within boiler min and max flow rates.
  2. Recommended pumps for WB1B 26 and 35: Grundfos 15-58 (3-speed) or Taco 00R, or equivalent.
  3. Fit a low-loss header when system flow is above the boiler maximum or below the minimum, or when flow is unknown. Viessmann prefers a low-loss header over closely spaced tees.
  4. Fit a pressure activated by-pass if any component in the heating circuit can isolate flow to the pump.
  5. For underfloor heating, install an immersion or strap-on aquastat in the low temperature loop downstream of the mixing valve to switch off the pump and/or boiler.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service Instructions, p. 36. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.