Viessmann Boiler: Route LON and low-voltage wiring away from mains
Route LON and low-voltage wiring away from mains on a Viessmann boiler: Electromagnetic interference can couple onto long wire runs. Keep LON wiring away from 120/240VAC conductors. If that is not possible, use stranded twisted-pair shielded wire and ground only one end of the shield.
Applies to: Versatronik 511 and 511D LON wiring
How to fix route lon and low-voltage wiring away from mains: step by step
- Keep LON wires clear of 120/240VAC conductors.
- If they must run close, use stranded twisted-pair shielded cable.
- Ground only one end of the shield.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 511 & 511D LON Type B manual, p. 5; p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.