Viessmann Boiler: Rooms too cold
Rooms too cold on a Viessmann boiler: Work through these causes in order. The control unit may be off, misset, or faulted, or the mixer motor may be stuck.
Applies to: Vitotronic 200-H heating circuit
Common causes of rooms too cold
- Heating circuit is switched off
- Power disconnect switched off
- Fuse or breaker tripped inside electrical panel
- Control unit settings incorrect (heating circuit on, room temperature, time, heating curve)
- Control unit fault (fault symbol U flashes)
- Mixer motor faulty
How to fix rooms too cold: step by step
- Press the ON/OFF button to turn the control unit on (see start-up).
- Switch on the power disconnect if one is installed outside the boiler room.
- Check the fuse or breaker inside the electrical panel; if it has tripped, notify the heating contractor.
- Check heating circuit is on, then the room temperature, time program and heating curve settings, and correct as needed.
- If the fault symbol U flashes, scan the fault code and notify the heating contractor.
- If the mixer motor is faulty: unlock motor lever A and operate mixer lever B by hand, then notify the heating contractor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H operating instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.