Viessmann Boiler: Rooms are too cold

Updated · by Aurora Star Tech Inc.

Rooms are too cold on a Viessmann boiler: Heating is off or the control or remote settings are wrong, or there is no fuel.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 200 and 300-K

Common causes of rooms are too cold

  • Heating system switched off at a control unit or mains isolator.
  • Fuse or MCB tripped.
  • Control unit or remote control set wrong.
  • DHW priority active, or DHW tank still heating.
  • Slab curing function active (not used).
  • No fuel: low oil or LPG, or gas shut-off closed.
  • Fault active on the boiler.

How to fix rooms are too cold: step by step

  1. Set the ON/OFF switches at all control units to ON.
  2. Turn on the mains isolator if installed.
  3. Check the fuse/MCB and reset or replace if needed.
  4. On the Vitotronic 200, make sure the heating symbol is set.
  5. On the 300-K, check heating and DHW mode, room temperature, time, time program and heating curve.
  6. Check the remote control settings if fitted.
  7. Check fuel reserves and reorder if needed, or open the gas shut-off valve.
  8. If a fault shows, scan and note the code, acknowledge it, and call the heating contractor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 200

HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B

Vitotronic 300-K

MW1SVitotronic 300-K, type MW2B

Source: Vitotronic 200 and 300-K Operating Instructions, p. 35. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977