Viessmann Boiler: Room air dependent combustion air supply
Room air dependent combustion air supply on a Viessmann boiler: Provide enough fresh combustion and ventilation air in the mechanical room. The room should never be under negative pressure. Exhaust, attic or dryer fans can pull air out faster than it can enter, so corrective air supply may be needed. Do not cover the boiler or store debris near it.
Applies to: Room air dependent venting
Common causes of room air dependent combustion air supply
- Exhaust, attic or dryer fans creating negative pressure
- Louvers or openings blocked or undersized
How to fix room air dependent combustion air supply: step by step
- Locate the boiler near an outside wall where fresh air can be ducted directly.
- Size ducts using national codes. Round ducts are allowed.
- Check the free area of closet louvers. If unknown, assume 20 percent for wood louvers and 60 to 75 percent for metal louvers.
- Enlarge the opening to make up for louver blockage. Example: a 14 x 6 in free opening needs a 14 x 10 in opening with metal louvers.
- Test for negative pressure with fans running and add make-up air if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.