Viessmann Boiler: Return valve protection with low-loss header (Circuit Diagram 8)
Return valve protection with low-loss header (Circuit Diagram 8) on a Viessmann boiler: When return temperature falls below the minimum, the return valve on the boilers closes proportionally via sensor T1 to protect the boiler.
Applies to: Circuit Diagram 8, multi-boiler system with low-loss header
Common causes of return valve protection with low-loss header (circuit diagram 8)
- Return temperature below required minimum
How to fix return valve protection with low-loss header (circuit diagram 8): step by step
- Verify sensor T1 is connected at plug aJA and coding 4A is set to 4A: 1.
- Verify continuous return temperature control is set (0C: 1).
- Size each boiler circuit pump so its supply is at least equal to the maximum possible total heating circuit supply; recommendation is 110%.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.