Viessmann Boiler: Return valve control for return temperature (circuit diagram 4)
Return valve control for return temperature (circuit diagram 4) on a Viessmann boiler: Return valve method for systems with no way to change the downstream heating circuits, such as older systems.
Applies to: Single-boiler system with shunt pump and return valve
Common causes of return valve control for return temperature (circuit diagram 4)
- Return temperature falls below the required minimum value
How to fix return valve control for return temperature (circuit diagram 4): step by step
- Check that sensor T2 switches the shunt pump on when the return is low.
- If the minimum return temperature is still not reached, check that the return valve closes proportionally via sensor T1.
- Confirm coding 0C: 1 is set for continuous return temperature control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.