Viessmann Boiler: Return temperature control with shunt pump and return valve
Return temperature control with shunt pump and return valve on a Viessmann boiler: Used where the distributor is close to the boiler and boiler water flow must be reduced.
Applies to: System type 2 with Vitorond 200 VD2 and modulating burner
How to fix return temperature control with shunt pump and return valve: step by step
- When the return temperature drops below the required minimum, sensor T2 switches on the shunt pump.
- If the minimum return temperature is still not reached, sensor T1 proportionally closes the return valve.
- Check that the minimum return temperature is held after the valve closes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.