Viessmann Boiler: Resetting the service display after maintenance
Resetting the service display after maintenance on a Viessmann boiler: The service display is cleared by changing coding 24. If coding 24 is not reset, the service display comes back on Monday morning.
Applies to: Vitotronic 100 GC1 boiler control
Common causes of resetting the service display after maintenance
- Service interval reached (flue gas temperature, burner hours or time interval).
How to fix resetting the service display after maintenance: step by step
- Set coding 24 to 1 if service is done before the service display appears, then set it back to 0.
- Reset the burner hours and burner starts with the reset button, then confirm.
- If needed, press and hold the two buttons together for about 4 seconds and reset the maximum flue gas temperature to the actual value.
- Set coding 24 back to 0 after maintenance.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.