How to fix reset the service display: step by step

  1. If service is done before the Service message shows, set coding 24: 1, then set 24: 0.
  2. Press the scan button to start the service scan.
  3. Scroll through service messages and confirm Acknowledge: Yes with OK.
  4. Press the exit button to end the service scan.
  5. After maintenance, set coding 24 from 1 back to 0.
  6. Reset burner hours, starts and fuel use from the operating status scan if needed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More reset & cancel tips for boiler

Source: Vitotronic 300 GW2 installation and service instructions, p. 78. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.