Viessmann Boiler: Replacing the rotary damper and servomotor
Replacing the rotary damper and servomotor on a Viessmann boiler: Removing and refitting the air damper assembly on the burner.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner air damper
How to fix replacing the rotary damper and servomotor: step by step
- Disconnect the servomotor connector.
- Undo the 4 screws on the rotary damper retaining bracket (torque 13 lb.in / 1.5 Nm) and remove the damper with its bracket.
- Undo the 2 screws on the servomotor axis (torque 3 lb.ft / 4 Nm) and remove the servomotor.
- Release the articulated rod on the rotary damper with an open-ended wrench.
- Fit the new rotary damper, air pressure switch and servomotor in reverse order.
- Check that the rotary damper is fully open when the burner is off and when it is running. If not, adjust it with the articulated rod and check the servomotor settings.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.