Viessmann Boiler: Replacing the printed circuit board (cascade electronics)

Updated · by Aurora Star Tech Inc.

Replacing the printed circuit board (cascade electronics) on a Viessmann boiler: Replacement of the cascade electronics printed circuit board. Record and restore settings.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300-K MW1S cascade electronics module A2

How to fix replacing the printed circuit board (cascade electronics): step by step

  1. Record all coding and adjustments made at the control unit.
  2. Replace the printed circuit board.
  3. Set coding 8A to 176.
  4. Set coding address 92 to 92:160.
  5. Re-enter the recorded coding and adjustments.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitotronic 300-K MW1S installation and service instructions, p. 119. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.