Viessmann Boiler: Replacing the PC board
Replacing the PC board on a Viessmann boiler: Procedure for swapping the Vitocontrol-C PC board, including how to restore the model-specific coding.
Applies to: HK1S and HK3S
How to fix replacing the pc board: step by step
- Record all codes and adjustments made at the control unit.
- Replace the PC board.
- Set code 8A:176 and coding address 92 to 92:172 for model HK1S, or 92:173 for model HK3S.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H Installation and Service Instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.