Viessmann Boiler: Replace gas valve
Replace gas valve on a Viessmann boiler: Install the new valve in the same orientation as the original. The gas pressure switches GDW1 and GDW2 are on the valve assembly.
Applies to: CA3B Series 2.5 to 6.0
How to fix replace gas valve: step by step
- Disconnect the screws and connectors from the gas valve and both gas pressure switches.
- Pull the compensation line from the gas valve.
- Remove the nuts on the gas line flange and remove the flange.
- Remove the nuts on the Venturi flange and remove the flange.
- Install in reverse order, checking orientation.
- Replace the gaskets on the inlet and outlet sides.
- Secure the valve on the flange with screws, torque 13 lb.in (1.5 Nm), without stress on the flange.
- Do not interchange the connecting cables of GDW1 and GDW2.
- Check all fittings for gas tightness.
- Do not let leak detection spray touch electrical contacts.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.