Viessmann Boiler: Replace combustion fan
Replace combustion fan on a Viessmann boiler: Fan removal with the Venturi pipe and gas valve.
Applies to: CA3B 2.5 to 6.0
How to fix replace combustion fan: step by step
- Disconnect both fan connectors.
- Remove the 6 nuts on the Venturi pipe and remove the Venturi pipe with the fitted gas valve. Tighten to 4.5 lb.ft (6 Nm) on reassembly.
- Undo the hex nuts from the 4 studs.
- Remove the fan and note how the gasket sits.
- Install in reverse order. Fit the gasket in the correct position.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.