Viessmann Boiler: Removing an existing boiler from a common vent
Removing an existing boiler from a common vent on a Viessmann boiler: Checks to run when an existing boiler is taken out of a shared vent with other gas appliances, so the remaining appliances still vent safely.
Applies to: Vitorond 200 VD2A
Common causes of removing an existing boiler from a common vent
- Common vent is likely oversized once the boiler is removed.
How to fix removing an existing boiler from a common vent: step by step
- Seal any unused openings in the common venting system.
- Inspect the vent for proper size, horizontal pitch, blockage, leakage and corrosion.
- Close building doors, windows and doors to other spaces. Run exhaust fans at maximum, but not a summer exhaust fan. Close fireplace dampers to test for negative pressure.
- Run the remaining appliance on high fire, with its thermostat set so it runs continuously.
- After 5 minutes at high fire, check for spillage at the barometric draft control relief opening with a match, candle or approved tester.
- Restore doors, windows, fans, dampers and other appliances to their previous state.
- Correct any venting problem so the installation meets the National Fuel Gas Code, ANSI Z223.1. If resizing, use Appendix G tables in that code.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A installation instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.