Viessmann Boiler: Reinstall turbulators and close the boiler
Reinstall turbulators and close the boiler on a Viessmann boiler: Seat the turbulators correctly and close the door evenly.
Applies to: All VD2 sizes 320 to 1080
How to fix reinstall turbulators and close the boiler: step by step
- On VD2-320 to VD2-860, push the first turbulator element about two thirds into the flue passage, then hook in and push in the second and third elements.
- Tighten the combustion chamber door bolts in a cross pattern. Do not overtighten.
- With a gas power burner, reconnect the gas train and run leak detection tests.
- Reinstall the clean-out opening covers.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.