Viessmann Boiler: Refit burner and check all gas equipment for leaks
Refit burner and check all gas equipment for leaks on a Viessmann boiler: Final check after burner refit. Only use approved leak detection products and remove residue afterward.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix refit burner and check all gas equipment for leaks: step by step
- Insert the burner and tighten the four nuts evenly and crosswise to 3 lb.ft (4 Nm).
- Fit the gas supply pipe with a new gasket and tighten to 11 lb.ft (15 Nm).
- Plug in the ventilation air intake adaptor.
- Reconnect the electrical leads.
- Check all gas equipment for tightness at operating pressure with an approved leak detection agent.
- Do not use leak detectors containing nitrites or sulphides. Remove all residue after testing.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.