Viessmann Boiler: Raising return temperature with a shunt pump (circuit diagram 3)

Updated · by Aurora Star Tech Inc.

Raising return temperature with a shunt pump (circuit diagram 3) on a Viessmann boiler: Shunt pump control to keep the boiler return temperature above the required minimum.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Single-boiler system with shunt pump and mixing valve

Common causes of raising return temperature with a shunt pump (circuit diagram 3)

  • Return temperature falls below the required minimum value

How to fix raising return temperature with a shunt pump (circuit diagram 3): step by step

  1. Check that sensor T2 is connected and switches the shunt pump on when the return is low.
  2. If the minimum return temperature is still not reached, reduce the boiler supply by at least 50% using sensor T1.
  3. Size the shunt pump so that bypassed water is about 30% of the boiler's total supply rate.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Vitotronic 100 GC1 installation and service instructions, p. 12. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.