Viessmann Boiler: Pressure relief valve piping
Pressure relief valve piping on a Viessmann boiler: Mount the pressure relief valve on the top of the boiler or on the boiler safety supply. Do not install valves, shut-offs or obstructions between the boiler and the relief valve or on its discharge. The discharge must be the same size as the outlet, run horizontally over the side of the boiler and then down to about 1 ft. (300 mm) above the floor, as close to a floor drain as possible. Do not pipe it outdoors or to any area that can freeze.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
How to fix pressure relief valve piping: step by step
- Mount the relief valve on the top of the boiler or its safety supply.
- Keep the outlet clear of any valve or obstruction.
- Pipe the discharge the same size as the outlet, horizontally then vertically down to about 1 ft. (300 mm) above the floor.
- Run the discharge close to a floor drain and secure it with hangers or brackets.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.