Viessmann Boiler: Pressure relief valve discharge piping
Pressure relief valve discharge piping on a Viessmann boiler: No valve may be installed between the pressure relief valve and the boiler. Discharge piping must be sized and routed per the ASME code and drained safely.
Applies to: Boiler pressure relief valve piping
How to fix pressure relief valve discharge piping: step by step
- Do not install any valve between the relief valve and the boiler.
- Make the discharge pipe full size of the valve outlet, as short and straight as possible.
- Place any elbow close to the valve outlet.
- Route discharge so no one can be scalded and so the pipe can be drained.
- Keep the pipe size and layout so pressure cannot reduce relieving capacity.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.