Viessmann Boiler: Power supply connection to the control
Power supply connection to the control on a Viessmann boiler: The control needs 120 VAC, single phase, 60 Hz, with grounding. Overcurrent protection of at least 6 A and a 2-pole disconnect must be on the supply.
Applies to: Vitotronic 300-K power supply
How to fix power supply connection to the control: step by step
- Confirm the supply has a 2-pole disconnect and at least 6 A overcurrent protection per local code.
- Connect line to terminal 11, neutral to N and ground to G on the DIN rail in the junction box.
- Check that L, N and G are not swapped.
- Verify the control is grounded before power-up.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.