Viessmann Boiler: Power Pump Module wiring and supply protection
Power Pump Module wiring and supply protection on a Viessmann boiler: Power supply must have overcurrent protection rated at most 15 A with a disconnect. The equipment must be grounded. Do not interchange the line, neutral and ground wires. Do not connect external equipment directly to the 120 VAC connectors; they are interface connections to the Power Pump Module only. Pump outputs are 120 VAC, 1 phase, 3 A max each; mixing valve motor is optional.
Applies to: Vitotronic 200 KW2 with Power Pump Module
How to fix power pump module wiring and supply protection: step by step
- Confirm the supply has max 15 A overcurrent protection and a disconnect.
- Ground the module.
- Check L, N and G are not swapped.
- Wire circulating pumps and the mixing valve motor to their marked terminals only.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 Service Instructions, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.