Viessmann Boiler: Piping layout: three zone circuits with low-loss header
Piping layout: three zone circuits with low-loss header on a Viessmann boiler: Boiler with DHW storage and three zone circuits. Total zone flow is above the boiler's maximum flow, so a low-loss header is required.
Applies to: Vitodens 200-W B2HA/B2HB with AM1 extension module
How to fix piping layout: three zone circuits with low-loss header: step by step
- Install a low-loss header. It is strongly recommended and sold as an accessory.
- Connect the DHW pump to output 21 and the boiler pump to output 20.
- Wire the thermostat for zone circuits 1, 2 and 3 as dry contacts.
- Connect zone circuit 1 to output 157.
- Connect zone circuits 2 and 3 to the outputs on the AM1 extension module (A1 and A2).
- Connect the outdoor sensor, DHW sensor and supply sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.