Viessmann Boiler: Piping layout: direct-connected heating circuit plus one system-separated circuit
Piping layout: direct-connected heating circuit plus one system-separated circuit on a Viessmann boiler: Boiler with one direct-connected heating circuit and one circuit separated by a plate heat exchanger, with DHW storage. The radiator circuit runs off the boiler pump, and the under-floor circuit is held to a lower temperature by a 3-way mixing valve.
Applies to: Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
How to fix piping layout: direct-connected heating circuit plus one system-separated circuit: step by step
- Confirm the combined flow of both heating circuits stays below the boiler's maximum water flow rate (see the boiler flow table on page 10).
- If the application flow may exceed the boiler maximum, or the system flow is unknown, install a low-loss header. It is an accessory.
- Size the plate heat exchanger so its secondary-side pressure drop is no more than the pressure drop of the 3-way mixing valve.
- Let the boiler pump supply the radiator circuit and the plate heat exchanger.
- Pipe the DHW recirculation pump so it pumps into the boiler.
- Run the mixing valve for the under-floor circuit through the accessory mixing-valve kit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.