Viessmann Boiler: Piping for heating and cooling applications
Piping for heating and cooling applications on a Viessmann boiler: When the boiler is used with a chiller or cooling coils in air handlers, the piping must keep chilled water out of the boiler.
Applies to: VD2-320 to VD2-1080
Common causes of piping for heating and cooling applications
- Chilled water entering the boiler
- Gravity circulation of boiler water during the cooling cycle
How to fix piping for heating and cooling applications: step by step
- Pipe the chilled medium in parallel with the boiler and install valves to keep chilled medium out of the boiler.
- On systems with heating coils in air handlers exposed to refrigerated air, install flow control valves or another automatic means to stop gravity circulation during cooling.
- At the start of cooling season, close valve V1 and open valve V2.
- At the start of heating season, close valve V2 and open valve V1.
- Attach a metal tag to these valves stating their purpose.
- Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
- Check the chiller manufacturer's installation instructions for further requirements.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.