Viessmann Boiler: Participant check (single-boiler system, LON error manager)
Participant check (single-boiler system, LON error manager) on a Viessmann boiler: Checks LON communication between the error manager control unit and the other system units. Only for single-boiler systems with LON.
Applies to: Vitotronic 100 GC1, single-boiler LON systems
How to fix participant check (single-boiler system, lon error manager): step by step
- Confirm the control unit is coded as error manager (coding 79: 1).
- Confirm the LON participant number is coded in all control units.
- Confirm the participant list is updated in the error manager.
- Press the w and OK buttons together for about 2 seconds to enter the participant check.
- Select the participant with the up or down button.
- Start the check with OK. Arrows stop flashing when communication is verified; if not, the error display appears.
- Repeat for further participants.
- Press w and OK together for about 1 second to start the check. All 7 arrows show and flash until it finishes; the display and lit buttons of the selected participant flash for about 60 seconds.
- Check the LON connection if the check fails.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.