Viessmann Boiler: Outdoor temperature sensor wiring
Outdoor temperature sensor wiring on a Viessmann boiler: Wire the outdoor sensor to the S1 terminals of the control.
Applies to: Outdoor temperature sensor, S1 input
How to fix outdoor temperature sensor wiring: step by step
- Mount the sensor on the outside of the structure.
- Connect field wire to the terminals inside the sensor and run it through the strain relief at the bottom of the housing.
- Refit the sensor cover onto the backing.
- Run the field wire from the sensor to the control.
- Connect the wires to the S1 terminals inside the control.
- Keep the wire away from 120/240 VAC conductors, or use shielded twisted pair with only one shield end grounded.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.