Viessmann Boiler: Outdoor temperature sensor placement and wiring
Outdoor temperature sensor placement and wiring on a Viessmann boiler: Mount the outdoor sensor on a north or north-west wall, 6 to 8 ft (2 to 2.5 m) above ground. In multi-storey buildings use the upper half of the second floor.
Applies to: All Vitocrossal 300 CA3B Dual Fuel models
How to fix outdoor temperature sensor placement and wiring: step by step
- Keep the sensor away from windows, doors and vent outlets, and away from balconies or gutters above it.
- Do not paint over the sensor.
- Wire it with 2-conductor cable, 18 AWG, to a maximum length of 115 ft (35 m).
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.