Viessmann Boiler: Outdoor temperature sensor mounting and wiring
Outdoor temperature sensor mounting and wiring on a Viessmann boiler: Mount the outdoor sensor on the north or northwest wall, away from openings and heat or water sources, and keep it unpainted and unplastered. Keep its cable away from line-voltage cable.
Applies to: Outdoor temperature sensor, Vitotronic 300
How to fix outdoor temperature sensor mounting and wiring: step by step
- Mount the sensor base 2 to 2.5 m (6.6 to 8.2 ft) above ground on the north or northwest wall.
- On multi-storey buildings, mount it in the upper part of the second floor.
- Keep the sensor away from windows, doors, air vents, balconies and drainage pipes.
- Do not paint or plaster over the sensor. If the wall is not yet plastered, allow for the plaster or remove the sensor first.
- Run the cable through the bushing, keeping it away from line-voltage cable.
- Connect the two wires to terminals 1 and 2 on the plug. The wires can be swapped.
- Insert the plug into socket 1 and apply strain relief.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 installation instructions, p. 13, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.