Viessmann Boiler: Outdoor sensor and DHW sensor installation notes
Outdoor sensor and DHW sensor installation notes on a Viessmann boiler: The outdoor sensor is field wired and must sit on the north or northwest wall, 2 to 2.5 m above ground. The DHW tank sensor is an immersion sensor with about 12 ft cable and is supplied ready to plug in. All pipe connections are field supplied.
Applies to: Vitodens 100-W B1HE and B1KE
How to fix outdoor sensor and dhw sensor installation notes: step by step
- Mount outdoor sensor on north or northwest wall, 80 to 100 in. above ground.
- Keep sensor cable clear of line voltage.
- Plug in DHW tank sensor and field-pipe the tank connections.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.