Viessmann Boiler: Oil piping to the burner
Oil piping to the burner on a Viessmann boiler: Piping must meet local codes, the burner and pump instructions, and CSA B139 in Canada or NFPA 31 in the USA. Oil supply pressure to the fuel unit must not exceed 3 psig.
Applies to: Oil supply to the VR1 burner
Common causes of oil piping to the burner
- Oil pressure above 3 psig can damage the fuel unit
- Teflon tape or compression fittings can cause valve failure or leaks
How to fix oil piping to the burner: step by step
- Use a pressure-limiting device on the oil supply.
- Do not use Teflon tape as pipe sealant. Use non-hardening joint compound on all threads.
- Do not use compression fittings.
- Run underground oil lines in encasement to prevent leaks into the ground.
- If any part of the tank is above burner level, install an anti-siphon device.
- Use swing joints or copper tubing at the tank connections.
- Connect the burner oil line with a flare fitting, leaving the burner door free to swing fully open.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service manual, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.