Viessmann Boiler: No response from the Modbus gateway
No response from the Modbus gateway on a Viessmann boiler: The master gets no reply from the gateway.
Applies to: Versatronik 502 / 502D gateway
Common causes of no response from the modbus gateway
- Baud/frame settings do not match 9600 8-N-1
- Rotary dial address is between two positions
- Communication cables have reversed polarity
How to fix no response from the modbus gateway: step by step
- Set the connection to 9600 8-N-1.
- Check the rotary dial for the device address and make sure it sits on a position, not between two.
- Check that A and B polarity matches on all cables.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 502 & 502D MODBUS manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.