Viessmann Boiler: Mount the outdoor temperature sensor
Mount the outdoor temperature sensor on a Viessmann boiler: Mount the sensor on a north or north-west wall, 2 to 2.5 m (6.5 to 8 ft) above ground. On multi-storey buildings use the upper half of the second storey.
Applies to: Outdoor temperature sensor
How to fix mount the outdoor temperature sensor: step by step
- Keep the sensor away from windows, doors, air vents, balconies and guttering.
- Do not paint over the sensor housing.
- Remove the cap and mount the bottom part of the sensor housing.
- Pull the sensor wire through the opening in the terminal compartment and through the strain relief.
- Connect the wires to the terminals.
- Refit the cap over the sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 Installation and Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.