Viessmann Boiler: Mount and wire the outdoor temperature sensor
Mount and wire the outdoor temperature sensor on a Viessmann boiler: Place the sensor where it reads outdoor air and not heat from the building.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix mount and wire the outdoor temperature sensor: step by step
- Remove the cover from the outdoor temperature sensor.
- Mount the wall base with the cable entry pointing down.
- Run the cable from the boiler control board to the sensor and connect it to the sensor terminals.
- Mount the sensor 6.6 to 8.2 ft. (2 to 2.5 m) above ground on the north or northwest wall.
- On a multi-storey building, mount it in the upper half of the second floor.
- Keep the sensor away from windows, doors, air vents, and under balconies or gutters.
- Do not cover the sensor with plaster. If the wall is not yet plastered, allow for plaster thickness or remove the sensor before plastering.
- Remove the X3 plug from the control board, attach the sensors, reinsert the X3 plug, then reinstall the control cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A installation manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.