Viessmann Boiler: Mixing valve motor turns in the wrong direction
Mixing valve motor turns in the wrong direction on a Viessmann boiler: Mixing valve on an extension kit heating circuit does not respond correctly. The flow temperature rises or falls in the wrong way during the valve check.
Applies to: Extension kit for heating circuit with mixing valve
Common causes of mixing valve motor turns in the wrong direction
- Motor rotation direction is wrong
- Mixing valve set is fitted incorrectly
How to fix mixing valve motor turns in the wrong direction: step by step
- Disconnect main power before opening the boiler.
- Power up. The boiler runs a self-test during which the mixing valve opens and closes.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature. If it drops, the motor direction is wrong or the valve set is fitted incorrectly.
- To reverse the motor direction, remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals "|" and "~".
- Refit the casing cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.