Viessmann Boiler: Measure static and running gas pressure
Measure static and running gas pressure on a Viessmann boiler: Check supply pressure at the gas combination valve inlet port A before and during operation.
Applies to: Vitocrossal 300 CU3A gas supply
How to fix measure static and running gas pressure: step by step
- Remove the boiler enclosure panel as shown on p. 11.
- Close the field-supplied gas shutoff valve.
- Loosen the screw at inlet gas pressure port A on the gas combination valve, do not remove it fully, and connect a manometer.
- Open the gas shutoff valve.
- Measure static pressure. Maximum is 14 in. w.c. for NG and 14 in. w.c. for LPG.
- Record the static reading in the Maintenance Record (p. 113).
- Start the boiler with the ON/OFF switch "8" (flip up the lower orange cover).
- Measure running pressure using a gauge resolving at least 0.04 in. w.c.
- Record the gas type and running pressure in the Maintenance Record (p. 113).
- Switch the boiler off, close the gas shutoff valve, remove the manometer and retighten the screw at port A.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.