Viessmann Boiler: Measure gas static and running pressure
Measure gas static and running pressure on a Viessmann boiler: Check the gas supply pressure at the gas combination valve before and during startup. Record the readings in the Maintenance Record on page 96.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix measure gas static and running pressure: step by step
- Remove the boiler enclosure panel as shown on page 12.
- Close the field-supplied gas shut-off valve.
- Loosen the screw at inlet gas pressure port A on the gas combination valve but do not remove it. Connect the manometer.
- Open the gas shut-off valve and measure the static pressure. Maximum is 14 in. w.c. for NG and 14 in. w.c. for LPG.
- Start the boiler with ON/OFF switch 8 and measure the running pressure. Use a gauge that reads at least 0.04 in. w.c. resolution.
- Record the gas type and readings. Switch the boiler off, close the gas valve, remove the manometer and retighten the port screw.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.