Match control unit to modulating burner on a Viessmann boiler: Measures burner output at the set points and enters the values into coding. The burner must already be adjusted. Set the minimum output as low as possible, taking the chimney/flue system into account.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Modulating burner start-up

How to fix match control unit to modulating burner: step by step

  1. Start up the burner.
  2. Press 9 and OK together for about 2 seconds.
  3. Use the up button to activate 'Modulating burner open' (display 2). Wait until the actuator is at maximum output.
  4. Record the maximum burner output from fuel consumption.
  5. Activate 'Modulating burner closed' (display 4) and time how long the actuator takes to reach minimum output.
  6. Record the minimum (basic) output from fuel consumption.
  7. Activate 'Modulating burner open' (display 2). After one-third of the time from step 5, activate 'Modulating burner neutral' (display 3).
  8. Record the partial output from fuel consumption.
  9. Press OK to end the relay test.
  10. Enter the recorded values into coding level 1 (see the modulating burner coding table).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

GC1KW10B

Source: Vitotronic 100 GC1 installation and service instructions, p. 90-91. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.