Viessmann Boiler: Match control to a modulating burner
Match control to a modulating burner on a Viessmann boiler: Measure burner output range on a running burner and enter the values in coding 1. The burner must be adjusted first. Keep minimum output as low as the flue system allows.
Applies to: Vitotronic 300 GW2 with modulating burner
How to fix match control to a modulating burner: step by step
- Start the burner.
- Press the menu and OK buttons together for about 2 seconds to start the relay test.
- Activate Burner mod. open and wait until the actuator reaches maximum output. Note the maximum output from fuel consumption.
- Activate Burner mod. closed and time how long the actuator takes to reach minimum output. Note that time in seconds.
- Note the minimum (basic) output from fuel consumption.
- Activate Burner mod. open again and stop the actuator after one third of the measured time. Note the partial output from fuel consumption.
- Press OK to end the relay test.
- Enter the values in coding 1 (see next setting).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 69-70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.