Viessmann Boiler: Lower the fixed high limit to 212 ºF / 100 ºC
Lower the fixed high limit to 212 ºF / 100 ºC on a Viessmann boiler: Field adjustment of the fixed high limit. Remove power first. Adjustment is permanent.
Applies to: Vitotronic 300 fixed high limit (Etheco/EGO)
How to fix lower the fixed high limit to 212 ºf / 100 ºc: step by step
- Remove the fuse.
- Unclip the cover at the four snap-in clips and remove it.
- Pull the front panel behind the cover upward and swing it open to the rear.
- Turn the slotted screw on the rear of the fixed high limit to 212 ºF / 100 ºC.
- Refit the front panel, cover and fuse.
- Check the box in the Vitotronic 300 service instructions to confirm the adjustment.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 installation instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.