Viessmann Boiler: Low water cut-off (LWCO) wiring
Low water cut-off (LWCO) wiring on a Viessmann boiler: A low water cut-off device is wired to the Power Pump Module. Its jumper must be removed first, and the function must be tested after installation.
Applies to: Low water cut-off device on Vitotronic 300 / Power Pump Module
How to fix low water cut-off (lwco) wiring: step by step
- Run a 3-conductor cable from the low water cut-off device to the Power Pump Module.
- Remove the jumper between terminals L/P1 and P2 on the Power Pump Module board.
- Wire the device as shown in the manual. The contact closes on water.
- After installation, check that the LWCO function works.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 installation instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.