Viessmann Boiler: Low water cut-off connection (VD2/VD2A/CT3)
Low water cut-off connection (VD2/VD2A/CT3) on a Viessmann boiler: Wire an external low water cut-off device to the control.
Applies to: VD2, VD2A and CT3
How to fix low water cut-off connection (vd2/vd2a/ct3): step by step
- Disconnect power to the control.
- Remove the jumper between terminals 12 and 15.
- Connect the LWCO device as shown in the diagram, and check its own manual for the interconnection details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.