Viessmann Boiler: LON wiring of the gateway to a Vitotronic 300 control
LON wiring of the gateway to a Vitotronic 300 control on a Viessmann boiler: Connect the gateway to the boiler control over LON and supply power. The manual gives 24VAC and 120VAC power options. Use the wiring diagram for the specific control.
Applies to: Vitotronic 300 GW5B, GW6B (single and cascade), 300-K MW2C (B2HA)
How to fix lon wiring of the gateway to a vitotronic 300 control: step by step
- Turn off power to the control and any damper or blower before working on it.
- Confirm the LON communication card is installed in the boiler control (required for Vitotronic 300-K MW2C and B2HA boilers).
- Plug the supplied CAT-5 cable (RJ45) into the RJ45 socket on the control and the other end into the RJ45 socket inside the gateway.
- Wire the field LON 2-wire connection to gateway terminals A and B.
- Power the gateway: field-supplied 24VAC supply, or the plug-in power cord for 120VAC gateways.
- Use the wiring diagram for the specific control model to confirm connections before restoring power.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 581 LON gateway manual, p. 8-12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.