LON wiring in line topology on a Viessmann boiler: The Viessmann LON system uses line bus topology with an end-of-line resistor at both ends. Two wires plus shielding are always required; the wires are interchangeable.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300-K MW1S LON system

How to fix lon wiring in line topology: step by step

  1. Connect each control unit or Vitocom in a line with Viessmann LON cable part no. 7143 495.
  2. Keep the cable run between devices at 7 m / 23 ft or less for direct cable connections.
  3. Fit an end-of-line resistor (part no. 7143 497) at both ends of the line. One is supplied with the Vitotronic 300-K MW1S.
  4. When using LON couplings (part no. 7143 496), no more than 3 cables may be used between two devices.
  5. Keep the wires and shielding intact on every connection.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 68. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.