Viessmann Boiler: LON network wiring
LON network wiring on a Viessmann boiler: Viessmann LON uses line BUS topology with end-of-line resistors at both ends. The two wires and shielding are always required; wires are interchangeable. Follow FTT-10A cabling rules.
Applies to: LON communication
How to fix lon network wiring: step by step
- Use Viessmann LON cable part 7143 495 between control units or Vitocom.
- Fit end-of-line resistor part 7143 497 at both ends of the line.
- Use the LON extension jack part 7143 496 for coupling; max 3 cables between two devices.
- For on-site cable extensions up to 900 m / 3000 ft, use junction boxes; up to 99 participants.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100
Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 86-87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.