Viessmann Boiler: LON daisy chain wiring to Vitotronic NR2
LON daisy chain wiring to Vitotronic NR2 on a Viessmann boiler: The Versatronik 503 connects into the Vitotronic NR2 LON daisy chain through one of its two RJ45 (8P8C) jacks. Both jacks are linked internally, so either can be used. If the module is at the end of the bus, a LON end resistor (not supplied) goes into the open jack.
Applies to: Versatronik 503 LON connection
How to fix lon daisy chain wiring to vitotronic nr2: step by step
- Connect the LON cable from the previous device to one RJ45 jack on the Versatronik 503.
- Connect the next device in the chain to the other RJ45 jack, or leave it open if this is the last device.
- If the module is at the end of the bus, fit a LON end resistor (supplied separately) in the unused jack.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.